12.2.3 External trafficable structures
Part 12.2 Construction in alpine areas · NCC 2019: 3.10.4.3
External stairways, ramps, access bridges or other trafficable structures serving the building must have—
a floor surface that consists of expanded mesh if it is used as a means of egress; and
any required barrier designed so that its sides are not less than 75% open; and
for a stairway, goings (G), risers (R) and slope relationship quantity (2R + G) in accordance with—
Table 11.2.2a; or
Table 12.2.3; and
for a ramp serving an external doorway, a gradient not steeper than 1:12.
Table 12.2.3 Alternative stair riser and going dimensions
Maximum risers (R) (mm)
Minimum risers (R) (mm)
Maximum going (G) (mm)
Minimum going (G) (mm)
Maximum slope relationship (2R + G) (mm)
Minimum slope relationship (2R + G) (mm)
150
115
375
355
675
605