5.2.6 Engaged piers
Part 5.2 Masonry veneer · NCC 2019: 3.3.5.14
Where engaged piers are installed to support subfloor framing, they must comply with the provisions of this Part and be constructed as follows:
Footings for piers must comply with Section 4.
Engaged piers must not support more than a single storey with a roof framing span of not more than 12 m.
Piers must be spaced at not more than 3 m centres with floor framing complying with—
H1D6(3) for steel framing; and
H1D6(4) for timber framing; and
H1D6(5) for structural steel framing.
Piers must be—
not more than 1.2 m high; and
a minimum thickness of 100 mm inclusive of mortar; and
a width greater than the depth of the timber or steel section which it is supporting (see Figure 5.2.6).
Notwithstanding (c), engaged piers must be located beneath—
each side of window and door openings; and
concentrated roof loads, inclusive of any roof beams and girder trusses.
Piers must be tied or bonded to the external masonry wall, and where ties are used they must comply with 5.6.5.
Piers formed from hollow-core masonry units must be filled with grout.
Figure 5.2.6 Engaged pier