Housing Provisions clause · ABCB Housing Provisions 2022

5.6.2 Masonry units

Part 5.6 Masonry components and accessories · NCC 2019: 3.3.5.3

Open 5.6.2 on NCC Online ↗

(1) Masonry veneer masonry units must have a minimum compressive strength of—

3 MPa for solid or cored units; or

10 MPa for hollow units.

(2) Cavity masonry and single skin masonry units must have a minimum compressive strength of—

5 MPa for solid or cored units; or

10 MPa for hollow units.

(3) Masonry cavity walls must have a minimum leaf thickness of 90 mm.

(4) Subject to (5), masonry units must be—

either clay or calcium silicate brick or concrete brick or block; and

classified and used in the exposure conditions appropriate to their classification as described in (6).

(5) Mixing of panels consisting of clay masonry units with panels consisting of concrete or calcium silicate masonry units is not permitted unless—

at vertical junctions, a control joint is installed; and

at horizontal junctions between panels of different materials, a slip joint using a membrane similar to that used for damp-proof courses is installed.

(6) Masonry unit exposure classifications and corresponding masonry unit applications are as follows:

Protected (P) masonry units are suitable for use in locations such as—

internal walls; and

external walls that are coated or rendered; and

walls above damp-proof courses provided the wall is protected at the top by a roof, eaves, coping, topping or the like.

General Purpose (GP) masonry units are suitable for use in all locations except those where ‘Exposure class’ (Exp) is required.

Exposure class (Exp) masonry units are suitable for use in all locations including severe local conditions such as—

below the damp-proof course in areas where walls are expected to be attacked by salts in the ground water or masonry itself (salt attack or salt damp); and

on sea fronts where walls are exposed to attack from salt spray; and

in heavily polluted areas subject to deposition of atmospheric pollution; and

under regular cyclic freeze and thaw conditions.