7.2.7 Flashings and cappings
Part 7.2 Sheet roofing · NCC 2019: 3.5.1.7
(1) Sheet metal roof flashings and cappings must comply with the following:
Roof flashings and cappings must be purpose made, machine-folded sheet metal sections of material compatible with all up and downstream metal roof covering materials in accordance with 7.2.2(2).
The type of fasteners for flashing and cappings must comply with 7.2.5.
The fastener and fixing frequency for flashings and cappings must comply with Table 7.2.7.
Joints in flashings and cappings must be not less than 75 mm, lapped in the direction of the fall of the roof, and fastened at intervals not more than 40 mm.
Wall and step flashings must be fastened into masonry walls with galvanized or zinc/aluminium sheet metal wedges at each end of each length and at intermediate intervals of not more than 500 mm and must overlap by not less than 75 mm in the direction of flow.
Lead flashings must not be used with prepainted steel or zinc/aluminium steel or on any roof if the roof is part of a drinking water catchment area.
Anti-capillary breaks must be installed in accordance with Figure 7.2.7a and be—
for flat surfaces – 10 mm/30 degree fold; and
all other surfaces – 10 mm/90 degree or 135 degree fold.
Acceptable flashing configurations are shown in Figure 7.2.7b and Figure 7.2.7c.
(2) Flashing of penetrations must comply with the following:
Collar flashings must permit the total drainage of the area above the penetration.
On completion of installation, the roof structure must be restored to its original strength by installing roof trimmers and soaker supports as necessary.
The type of fasteners for flashings and cappings must comply with 7.2.5.
Lead flashings must not be used with prepainted steel or zinc/aluminium steel or on any roof if the roof is part of a drinking water catchment area.
Acceptable flashings for penetrations are shown in Figure 7.2.7d, Figure 7.2.7e and Figure 7.2.7f.
Clearance for heating appliance roof support members must be in accordance with Part 12.4.
Table 7.2.7 Fastener frequency for flashings and cappings
Roof type
Fixing frequency
Fastener type
Concealed fastener roofs
Every rib
Rivets and self-drilling screws
Pierced fastener roofs
Every second rib
Self-drilling screws or rivets
Corrugated roofs
Every fourth rib
Self-drilling screws or rivets
Figure 7.2.7a Anti-capillary breaks
Figure 7.2.7b Parapet flashing—Acceptable flashing details
Figure 7.2.7c Parapet and end wall flashing—Acceptable flashing details
Figure 7.2.7d PVC aprons—Typical roof penetration flashing details
Figure 7.2.7e Collar flashings—Typical roof penetration flashing details
Figure 7.2.7f Large penetrations using apron—typical roof penetration flashing details
Tables
Clauses referred to
- 7.2.2 Corrosion protection and compatibility requirements for roofing
- 7.2.5 Fixing of metal sheet roofing