New South Wales variation · ABCB Housing Provisions 2022
NSW 13.2.5 External walls
Part 13.2 Building fabric · varies 13.2.5 External walls
Delete clause 13.2.5 and insert NSW 13.2.5 as follows:
(1) A metal-framed wall that forms part of the building envelope must have a thermal break, consisting of a material with an R-Value of not less than R0.2, installed at all points of contact between the external cladding and the metal frame if the wall—
does not have a wall lining or has a wall lining that is fixed directly to the metal frame; and
is clad with weatherboards, fibre-cement or the like, or metal sheeting fixed to the metal frame.
(2) The requirements of (1) do not apply to walls constructed using insulated sandwich panels.
Not in NCC 2025. No NSW 13.2.5 in ABCB Housing Provisions 2025.