C4D3 Protection of openings in external walls
Part C4 Protection of openings · NCC 2019: C3.2
(1) Subject to (2), openings in an external wall that is required to have an FRL must be protected in accordance with C4D5, and if wall-wetting sprinklers are used, they must be located externally.
(2) The requirements of (1) only apply if the distance between the opening and the fire-source feature to which it is exposed is less than—
3 m from a side or rear boundary of the allotment; or
6 m from the far boundary of a road, river, lake or the like adjoining the allotment, if not located in a storey at or near ground level; or
6 m from another building on the allotment that is not Class 10.
(3) Openings required to be protected under (1), must not occupy more than 1/3 of the area of the external wall of the storey in which they are located unless they are in a Class 9b building used as an open spectator stand.
Changed in NCC 2025. See NCC 2025 Volume One C4D3, or show what changed.
(1) Subject to (2), openings in an external wall, or openings in part of an external wall, where that external wall that or external wall part is required to have an FRL must be protected in … a Class 9b building used as an open spectator stand.
Removed words are struck through; added words are highlighted. Comparison of the text only.