Performance Requirement · NCC 2022 Volume One

E2P2 Safe evacuation routes

Part E2 Smoke hazard management · NCC 2019: EP2.2

Open E2P2 on NCC Online ↗

(1) In the event of a fire in a building the conditions in any evacuation route must be maintained for the period of time occupants take to evacuate the part of the building so that—

the temperature will not endanger human life; and

the level of visibility will enable the evacuation route to be determined; and

the level of toxicity will not endanger human life.

(2) The period of time occupants take to evacuate referred to in (1) must be appropriate to—

the number, mobility and other characteristics of the occupants; and

the function or use of the building; and

the travel distance and other characteristics of the building; and

the fire load; and

the potential fire intensity; and

the fire hazard; and

any active fire safety systems installed in the building; and

fire brigade intervention.

Limitations

E2P2 does not apply to an open-deck carpark or open spectator stand.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One E2P2.

Defined terms used