Deemed-to-Satisfy Provision · NCC 2022 Volume One
E4D7 Class 2 and 3 buildings and Class 4 parts: exemptions
Part E4 Visibility in an emergency, exit signs and warning systems · NCC 2019: E4.7
E4D5 does not apply to—
a Class 2 building in which every door referred to is clearly and legibly labelled on the side remote from the exit or balcony—
with the word “EXIT” in capital letters 25 mm high in a colour contrasting with that of the background; or
by some other suitable method; and
an entrance door of a sole-occupancy unit in a Class 2 or 3 building or Class 4 part of a building.
Same wording in NCC 2025 Volume One. See NCC 2025 Volume One E4D7.