Deemed-to-Satisfy Provision · NCC 2022 Volume One

E4D9 Emergency warning and intercom systems

Part E4 Visibility in an emergency, exit signs and warning systems · NCC 2019: E4.9

Open E4D9 on NCC Online ↗

An emergency warning and intercom system complying, where applicable, with AS 1670.4 must be installed—

in a building with an effective height of more than 25 m; and

in a Class 3 building having a rise in storeys of more than 2 and used as—

the residential part of a primary or secondary school; or

accommodation for the aged, children or people with a disability; and

in a Class 3 building used as a residential care building, except that the system—

must be arranged to provide a warning for occupants; and

in areas used by the residents, may have its alarm adjusted in volume and content to minimise trauma consistent with the type and condition of residents; and

in a Class 9a building having a floor area of more than 1000 m2 or a rise in storeys of more than 2, and the system—

must be arranged to provide a warning for occupants; and

in a ward area, may have its alarm adjusted in volume and content to minimise trauma consistent with the type and condition of patients; and

in a Class 9b building—

used as a school and having a rise in storeys of more than 3; or

used as a theatre, public hall, or the like, having a floor area more than 1000 m2 or a rise in storeys of more than 2.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One E4D9.
Can't meet E4D9? A Performance Solution must meet the Performance Requirements it satisfies: E4P1, E4P2, E4P3. Start a Performance Solution →