E4V1 Emergency lighting
Part E4 Visibility in an emergency, exit signs and warning systems · NCC 2019: EV4.1
(1) Compliance with E4P1 is verified for the level of visibility for safe evacuation in an emergency and instantaneous activation, when an emergency lighting system satisfies the requirements of (2) to (5).
(2) The calculated horizontal illuminance is not less than—
0.2 lux at floor level in the path of travel to an exit; and
1 lux at each floor level or tread in every required—
fire-isolated stairway; or
fire-isolated passageway; or
fire-isolated ramp; or
non-fire-isolated stairway; or
non-fire-isolated ramp.
(3) The emergency lighting provides a level of illuminance not less than—
10% of that required by (2) within 1 second of energisation; and
80% of that required by (2) within 15 seconds of energisation.
(4) The full level of illumination required by (2) must be achieved within 60 seconds of energisation.
(5) An emergency lighting system must operate at not less than the minimum required level of illuminance for not less than 90 minutes.