Deemed-to-Satisfy Provision · NCC 2022 Volume One

F2D2 Wet area construction

Part F2 Wet areas and overflow protection · NCC 2019: F1.7(a) and (b)

Open F2D2 on NCC Online ↗
Varied in SA. Check the variation for your state.

(1) In a Class 2 and 3 building and a Class 4 part of a building, building elements in wet areas must—

be water resistant or waterproof in accordance with Specification 26; and

comply with AS 3740.

(2) In a Class 5, 6, 7, 8 or 9 building, building elements in a bathroom or shower room, a slop hopper or sink compartment, a laundry or sanitary compartment must—

be water resistant or waterproof in accordance with Specification 26; and

comply with AS 3740,

as if they were in a Class 2 or 3 building or a Class 4 part of a building.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One F2D2.
Can't meet F2D2? A Performance Solution must meet the Performance Requirements it satisfies: F2P1, F2P2. Start a Performance Solution →