Performance Requirement · NCC 2022 Volume One
G1P4 Vaults
Part G1 Minor structures and components · NCC 2019: GP1.4
Any strong-room, vault or the like which is of sufficient size for a person to enter must—
have adequate means of communicating with or alerting other occupants in the building in the case of an emergency; and
have internal lighting controllable only from within the room; and
have an external indicator that the room is occupied.