G4D5 External trafficable structures
Part G4 Construction in alpine areas · NCC 2019: G4.5
External stairways, ramps, access bridges or other trafficable structures serving the building must—
have a floor surface that consists of expanded mesh if it is used as a means of egress; and
have any required barrier designed so that its sides are not less than 75% open; and
for a stairway, have goings (G), risers (R) and slope relationship quantity (2R + G) in accordance with—
Table D3D14; or
Table G4D5; and
for a ramp serving as an exit and not serving as an accessible ramp, have a gradient not steeper than 1:12; and
where a ramp is also serving as an accessible ramp under Part D4, be in accordance with AS 1428.1.
Table G4D5 Alternate stair riser and going dimensions
Riser (R)
Going (G)
Slope relationship (2R + G)
Max
Min
Max
Min
Max
Min
150
115
375
355
675
605
Table Notes
Dimensions are in mm.