Deemed-to-Satisfy Provision · NCC 2022 Volume One
G4D8 Fire orders
Part G4 Construction in alpine areas · NCC 2019: G4.9
Every Class 2, 3 or 9 building must display a notice clearly marked “FIRE ORDERS” in suitable locations near the main entrance and on each storey, explaining—
the method of operation of the fire alarm system and the location of all call-points; and
the location and methods of operation of all fire-fighting equipment; and
the location of all exits; and
the procedure for evacuation of the building.