Performance Requirement · NCC 2022 Volume One

G7P1 Livable housing design

Part G7 Livable housing design

Open G7P1 on NCC Online ↗

Each sole-occupancy unit in a Class 2 building must be provided with—

at least one level and step-free entrance door into the sole-occupancy unit from an accessible part of the floor on which it is located; and

internal doors and corridors which facilitate unimpeded movement between spaces; and

a sanitary compartment that—

facilitates independent access and use; and

is located on the entry level of the sole-occupancy unit; and

a shower that facilitates independent access and use; and

the walls of a sanitary compartment referred to in (c), the shower referred to in (d) and a bath (where installed, other than a freestanding bath) constructed so as to facilitate future installation of grabrails, or the like, in a way that minimises the removal of existing wall linings.

Applications

G7P1(a) only applies to a sole-occupancy unit that is located on an accessible floor.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One G7P1.