I1D4 Seating area
Part I1 Class 9b buildings · NCC 2019: H1.4
In a seating area—
the gradient of the floor surface must not be steeper than 1 in 8, or the floor must be stepped so that—
a line joining the nosings of consecutive steps does not exceed an angle of 30° to the horizontal; and
the height of each step in the stepped floor is not more than 600 mm; and
the height of any opening in such a step is not more than 125 mm; and
if an aisle divides the stepped floor and the difference in level between any 2 consecutive steps—
exceeds 230 mm but not 400 mm — an intermediate step must be provided in the aisle; and
exceeds 400 mm — 2 equally spaced intermediate steps must be provided in the aisle; and
the going of intermediate steps must be not less than 270 mm and such as to provide as nearly as practicable equal treads throughout the length of the aisle; and
the clearance between rows of fixed seats used for viewing performing arts, sport or recreational activities must be not less than—
300 mm if the distance to an aisle is not more than 3.5 m; or
500 mm if the distance to an aisle is more than 3.5 m.