Performance Requirement · NCC 2022 Volume One

J1P3 Energy usage of a sole-occupancy unit of a Class 2 building or a Class 4 part of a building

Part J1 Energy efficiency performance requirements

Open J1P3 on NCC Online ↗

(1) The energy value of the domestic services of a sole-occupancy unit of a Class 2 building or Class 4 part of a building must not exceed the energy value with—

a 3-star ducted heat pump, rated under the 2019 GEMS determination, heating all spaces that are provided with heating; and

a 3-star ducted heat pump, rated under the 2019 GEMS determination, cooling all spaces that are provided with cooling; and

a 5-star instantaneous gas water heater, rated under the 2017 GEMS determination, providing all domestic hot water; and

a lighting power density of 4 W/m2 serving all internal spaces that are provided with artificial lighting.

(2) Domestic services, including any associated distribution system and components must, to the degree necessary, have features that facilitate the efficient use of energy appropriate to—

the domestic service and its usage; and

the geographic location of the building; and

the location of the domestic service; and

the energy source.

Changed in NCC 2025. See NCC 2025 Volume One J1P3, or show what changed.

(1) The energy value of the domestic services of a sole-occupancy unit of a Class 2 building or Class 4 part of a building must not exceed the … the location of the domestic service; and the energy source.

Removed words are struck through; added words are highlighted. Comparison of the text only.