Specification clause · NCC 2022 Volume One
S13C4 Pipes penetrating sanitary compartments
Specification 13 Penetration of walls, floors and ceilings by services · NCC 2019: Spec C3.15: 4
If a pipe of metal or UPVC penetrates the floor of a sanitary compartment in accordance with C4D15(2)(c)(ii)—
the opening must be neatly formed and no larger than is necessary to accommodate the pipe or fitting; and
the gap between pipe and floor must be fire-stopped in accordance with S13C7.
Same wording in NCC 2025 Volume One. See NCC 2025 Volume One S13C4.