S16C5 Sling-style swimming pool lift
Specification 16 Accessible water entry/exit from swimming pools · NCC 2019: Spec D3.10: 5
A sling lift must comply with the following:
A sling lift must be located where the water depth is not more than 1300 mm.
When the sling is in the raised position and in the transfer position, the centreline of the sling must be located over the swimming pool surround and not less than 450 mm from the swimming pool edge.
The surface of the swimming pool surround between the centreline of the sling and the swimming pool edge must have a gradient of not more than 1:50 and must be slip-resistant.
A clear space must be provided on the swimming pool surround parallel with the swimming pool edge on the side remote from the water (see Figure S16C5a and Figure S16C5b) and must—
be not less than 900 mm x 1300 mm; and
have a gradient of not more than 1:50; and
have a slip-resistant surface; and
be located so that the centreline of the space is directly below the lifting point for the sling.
A sling lift must be capable of being operated from the swimming pool surround, within the swimming pool and from the sling.
A sling must be designed so that it will submerge to a water depth of not less than 500 mm below the stationary water level.
A sling lift must be designed to withstand a weight of not less than 136 kg and be capable of sustaining a static load not less than 1.5 times the rated load.