Specification clause · NCC 2022 Volume One

S1C2 Rating

Specification 1 Fire-resistance of building elements · NCC 2019: Sch. 5: 2

Open S1C2 on NCC Online ↗

A building element meets the requirements of this Specification if—

it is listed in, and complies with Tables S1C2a, S1C2b, S1C2c, S1C2d, S1C2e, S1C2f, S1C2g, S1C2h, S1C2i, S1C2j, S1C2k, S1C2l, S1C2m or S1C2n of this Specification as applicable; or

it is identical with a prototype that has been submitted to the Standard Fire Test, or an equivalent or more severe test, and the FRL achieved by the prototype without the assistance of an active fire suppression system is confirmed in a report from an Accredited Testing Laboratory which—

describes the method and conditions of the test and the form of construction of the tested prototype in full; and

certifies that the application of restraint to the prototype complied with the Standard Fire Test; or

it differs in only a minor degree from a prototype tested under (b) and the FRL attributed to the building element is confirmed in a report from an Accredited Testing Laboratory which—

certifies that the building element is capable of achieving the FRL despite the minor departures from the tested prototype; and

describes the materials, construction and conditions of restraint which are necessary to achieve the FRL; or

it is designed to achieve the FRL in accordance with—

AS/NZS 2327, AS 4100 and AS/NZS 4600 if it is a steel or composite structure; or

AS 3600 if it is a concrete structure; or

AS 1720.4 if it is a timber element other than fire-protected timber; or

AS 3700 if it is a masonry structure; or

the FRL is determined by calculation based on the performance of a prototype in the Standard Fire Test and confirmed in a report in accordance with S1C3; or

for fire-protected timber, it complies with Specification 10 where applicable.

Table S1C2a FRLs deemed to be achieved by walls — masonry

Masonry type

Minimum thickness (mm) of principal material for FRLs

60/60/60

90/90/90

120/120/120

180/180/180

240/240/240

Ashlar

-

-

-

-

300

Calcium silicate

See clause S1C2(d)(iv)

Concrete

Fired clay

Table Notes

For the purposes of this table, each element must meet the requirements of Specification 2.

Table S1C2b FRLs deemed to be achieved by walls — concrete

Concrete type

Minimum thickness (mm) of principal material for FRLs

60/60/60

90/90/90

120/120/120

180/180/180

240/240/240

No fines

-

-

-

150

300

Prestressed

See clause S1C2(d)(iv)

Reinforced

Plain

-

-

-

150

170

Table Notes

For the purposes of this table, each element must meet the requirements of Specification 2.

Table S1C2c FRLs deemed to be achieved by walls — gypsum

Gypsum type

Minimum thickness (mm) of principal material for FRLs

60/60/60

90/90/90

120/120/120

180/180/180

240/240/240

Solid gypsum blocks

75

90

100

110

125

Gypsum — perlite or gypsum vermiculite-plaster on metal lath and channel (non-loadbearing walls only)

50

50

65

-

-

Table Notes

For the purposes of this table, each element must meet the requirements of Specification 2.

Table S1C2d FRLs deemed to be achieved by concrete columns

Column type

Minimum thickness (mm) of principal material for FRLs

60/60/60

90/90/90

120/120/120

180/180/180

240/240/240

Prestressed

See clause S1C2(d)(ii)

Reinforced

Table S1C2e FRLs deemed to be achieved by hot-rolled steel columns (including a fabricated column) exposed on not more than 3 sides

Fire protection

Minimum thickness (mm) of principal material for FRLs

60/60/60

90/90/90

120/120/120

180/180/180

240/240/240

Concrete cast in-situ — loadbearing

25

30

40

55

75

Concrete cast in-situ — non-loadbearing unplastered

25

30

40

50

75

Concrete cast in-situ — non-loadbearing plastered 13 mm

25

25

30

40

50

Gypsum cast in-situ

-

-

-

-

50

Gypsum — perlite or gypsum-vermiculite plaster—sprayed to contour

20

25

35

50

55

Gypsum — perlite or gypsum-vermiculite plaster—sprayed on metal lath

20

20

25

35

45

Table Notes

For the purposes of this table, each element must meet the requirements of Specification 2.

Table S1C2f FRLs deemed to be achieved by hot-rolled steel columns (including a fabricated column) exposed on no more than 3 sides and with column spaces filled

Fire protection

Minimum thickness (mm) of principal material for FRLs

60/60/60

90/90/90

120/120/120

180/180/180

240/240/240

Solid calcium-silicate masonry

50

50

50

50

65

Solid clay masonry

50

50

50

65

90

Solid concrete masonry

50

50

50

65

90

Solid gypsum blocks

50

50

50

50

65

Hollow terracotta blocks — plastered 13 mm

50

50

50

65

90

Table Notes

For the purposes of this table, each element must meet the requirements of Specification 2.

Table S1C2g FRLs deemed to be achieved by hot-rolled steel columns (including a fabricated column) exposed on no more than 3 sides and with column spaces unfilled

Fire protection

Minimum thickness (mm) of principal material for FRLs

60/60/60

90/90/90

120/120/120

180/180/180

240/240/240

Solid calcium-silicate masonry

50

50

50

-

-

Solid clay masonry

50

50

65

-

-

Solid concrete masonry

50

50

65

-

-

Solid gypsum blocks

50

50

50

-

-

Hollow terracotta blocks — plastered 13 mm

50

50

65

-

-

Table Notes

For the purposes of this table, each element must meet the requirements of Specification 2.

Table S1C2h FRLs deemed to be achieved by hot-rolled steel columns (including a fabricated column) exposed on no more than 4 sides

Fire protection

Minimum thickness (mm) of principal material for FRLs

60/–/–

90/–/–

120/–/–

180/–/–

240/–/–

Concrete cast in-situ — loadbearing

25

40

45

65

90

Concrete cast in-situ — non-loadbearing unplastered

35

30

40

50

65

Concrete cast in-situ — non-loadbearing plastered 13 mm

25

25

30

40

50

Gypsum cast in-situ

-

-

-

-

50

Gypsum — perlite or gypsum-vermiculite plaster — sprayed to contour

25

30

40

55

65

Gypsum — perlite or gypsum-vermiculite plaster — sprayed on metal lath

20

20

30

40

50

Table Notes

For the purposes of this table, each element must meet the requirements of Specification 2.

Table S1C2i FRLs deemed to be achieved by hot-rolled steel columns (including a fabricated column) exposed on no more than 4 sides and with column spaces filled

Fire protection

Minimum thickness (mm) of principal material for FRLs

60/–/–

90/–/–

120/–/–

180/–/–

240/–/–

Solid calcium-silicate masonry

50

50

50

65

75

Solid clay masonry

50

50

50

75

100

Solid concrete masonry

50

50

50

75

100

Solid gypsum blocks

50

50

50

65

75

Hollow terracotta blocks — plastered 13 mm

50

50

50

75

100

Table Notes

For the purposes of this table, each element must meet the requirements of Specification 2.

Table S1C2j FRLs deemed to be achieved by hot-rolled steel columns (including a fabricated column) exposed on no more than 4 sides and with column spaces unfilled

Fire protection

Minimum thickness (mm) of principal material for FRLs

60/–/–

90/–/–

120/–/–

180/–/–

240/–/–

Solid calcium-silicate masonry

50

50

50

-

-

Solid clay masonry

50

50

65

-

-

Solid concrete masonry

50

50

65

-

-

Solid gypsum blocks

50

50

50

-

-

Hollow terracotta blocks — plastered 13 mm

50

50

65

-

-

Table Notes

For the purposes of this table, each element must meet the requirements of Specification 2.

Table S1C2k FRLs deemed to be achieved by concrete beams

Concrete type

Minimum thickness (mm) of principal material for FRLs

60/–/–

90/–/–

120/–/–

180/–/–

240/–/–

Prestressed

See clause S1C2(d)(ii)

Reinforced

Table S1C2l FRLs deemed to be achieved by hot-rolled steel beams (including an open-web joist, girder, truss, etc.) exposed on no more than 3 sides

Fire protection

Minimum thickness (mm) of principal material for FRLs

60/–/–

90/–/–

120/–/–

180/–/–

240/–/–

Concrete — cast in-situ

25

30

40

50

65

Gypsum — perlite or gypsum-vermiculite plaster — sprayed to contour

20

25

35

50

55

Gypsum — perlite or gypsum-vermiculite plaster — sprayed on metal lath

20

20

25

35

45

Table Notes

For the purposes of this table, each element must meet the requirements of Specification 2.

Table S1C2m FRLs deemed to be achieved by hot-rolled steel beams (including an open-web joist, girder, truss, etc.) exposed on 4 sides

Fire protection

Minimum thickness (mm) of principal material for FRLs

60/–/–

90/–/–

120/–/–

180/–/–

240/–/–

Concrete — cast in-situ

25

40

45

60

90

Gypsum — p

Tables

Changed in NCC 2025. See NCC 2025 Volume One S1C2, or show what changed.

A building element meets the requirements of this Specification if … — perlite or gypsum vermiculite-plaster on metal lath and channel (non-loadbearing (non-load bearing walls only) 50 50 65 - - Table Notes For … FRLs 60/60/60 90/90/90 120/120/120 180/180/180 240/240/240 Concrete cast in-situ — loadbearing load bearing 25 30 40 55 75 Concrete cast in-situ — non-loadbearing non-load bearing unplastered 25 30 40 50 75 Concrete cast in-situ — non-loadbearing non-load bearing plastered 13 mm 25 25 30 40 50 Gypsum cast … FRLs 60/–/– 90/–/– 120/–/– 180/–/– 240/–/– Concrete cast in-situ — loadbearing load bearing 25 40 45 65 90 Concrete cast in-situ — non-loadbearing non-load bearing unplastered 35 25 30 40 50 65 Concrete cast in-situ — non-loadbearing non-load bearing plastered 13 mm 25 25 30 40 50 Gypsum cast … 240/–/– Concrete — cast in-situ 25 40 45 60 90 Gypsum — p Gyp

Removed words are struck through; added words are highlighted. Comparison of the text only.