(1) The local fire indicator panel must be located in a central area, such as a reception area, so that it is readily accessible by staff at all times.

(2) The local fire indicator panel must be fixed wired.

(3) The local fire indicator panel must incorporate the following:

A suitable mains power supply with battery back-up (capable of operating the system for 12 hours) for the local fire indicator panel and extra-low voltage smoke alarms supplied directly from the local fire indicator panel.

Terminals for input signal conductors from the smoke alarm and residential sprinkler system and, if the signal source is from a low voltage smoke alarm, external isolation must be provided.

Visible indication of the alarm zone in which the actuating device is located.

Automatic audible and visible indication of the following faults:

A break in the wiring of any circuit between smoke alarms or sprinkler alarm switch and the local fire indicator panel.

Low battery condition.

Automatic visible indication of mains power failure.

Initiation of any ancillary control facilities such as smoke door release or air-conditioning shut-down.

Local operation of individual smoke alarms, in the event of alarm zone isolation at the local fire indicator panel.

(4) If the local fire indicator panel is also used for other non-fire related purposes such as security, then these functions—

must be on separate and distinct circuits; and

when disabled or isolated, must not interfere with the operation of fire alarm circuitry.

(5) The local fire indicator panel must comply with AS 1670.1.

(6) The local fire indicator panel must have the capacity to incorporate heat detectors deemed suitable in accordance with AS 1670.1 on either the same or separate alarm zones as the smoke alarms.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One S23C4.