S23C7 Wiring
Specification 23 Residential fire safety systems · NCC 2019: Spec E2.2d: 2(e)
(1) Smoke alarms and associated equipment must be fixed wired for low voltage or extra-low voltage wiring systems, as applicable.
(2) All extra-low voltage wiring must be red sheathed 0.6/1 kV stranded, with conductors having a cross sectional area of not less than 0.75 mm2.
(3) Clear and concise "as-installed" single line drawings to a suitable scale, showing rooms, external and internal walls, fixed partitions, doorways etc., are to be provided for each installation at the local fire indicator panel.
(4) Drawings must also include the actual location of fire alarms, smoke alarms, sprinkler flow switches (where installed), alarm connection points and local fire indicator panel, to enable easy identification of alarm system elements and their relationship to the building layout.
(5) Symbols used in the drawings referred to in (4) must be as shown in Figures S23C7a, S23C7b, S23C7c, S23C7d, S23C7e or S23C7f.
Figure S23C7a Flow switch symbol
Figure S23C7b Heat detector symbol
Figure S23C7c Smoke detector symbol
Figure S23C7d End-of-line device symbol
Figure S23C7e Fire indicator panel symbol
Figure S23C7f Smoke alarm symbol