S26C5 Areas adjacent to baths and spas without showers
Specification 26 Waterproofing and water-resistance requirements for building elements in wet areas · NCC 2019: Table F1.7
(1) For areas adjacent to a bath and spa, the following applies:
For concrete, compressed fibre-cement and fibre-cement sheet flooring, the floor of the room must be water resistant.
For timber floors including particleboard, plywood and other timber based flooring materials, the floor of the room must be waterproof.
Tap and spout penetrations must be waterproof where they occur in horizontal surfaces.
(2) For areas adjacent to a non-freestanding bath and spa, the following applies:
Walls must be water resistant—
to a height of not less than 150 mm above the vessel, for the extent of the vessel, where the vessel is within 75 mm of a wall; and
at all exposed surfaces below vessel lip.
Wall junctions and joints must be water resistant within 150 mm above a vessel for the extent of the vessel.
Wall/floor junctions must be waterproof for the extent of the vessel.
(3) For inserted baths and spas, the following applies:
For floors and horizontal surfaces:
Any shelf area adjoining the bath or spa must be waterproof and include a waterstop under the vessel lip.
There are no requirements for the floor under a bath or spa.
For walls:
Waterproof to not less than 150 mm above the lip of a bath or spa.
There are no requirements for walls beneath the lip of a bath or spa.
For wall junctions and joints:
Waterproof junctions within 150 mm of a bath or spa.
There are no requirements for junctions and joints in walls beneath the lip of a bath or spa.
Tap and spout penetrations must be waterproof where they occur in horizontal surfaces.