Specification clause · NCC 2022 Volume One

S2C13 Height-to-thickness ratio of certain walls

Specification 2 Descriptions of elements referred to in Specification 1 · NCC 2019: Sch. 5 (Annex): 5

Open S2C13 on NCC Online ↗

The ratio of height between lateral supports to overall thickness of a wall of ashlar, no-fines concrete, unreinforced concrete, solid gypsum blocks, gypsum-perlite or gypsum-vermiculite plaster on metal lath and channel, must not exceed—

20 for a loadbearing wall; or

27 for a non-loadbearing wall.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One S2C13.