Specification clause · NCC 2022 Volume One

S2C27 Measurement of thickness of column and beam protection

Specification 2 Descriptions of elements referred to in Specification 1 · NCC 2019: Sch. 5 (Annex): 12.1

Open S2C27 on NCC Online ↗

The thickness of the fire protection to steel columns and steel beams (other than fire protection of gypsum-perlite or gypsum-vermiculite plaster sprayed on metal lath or sprayed to contour) is to be measured from the face or edge of the steel, from the face of a splice plate or from the outer part of a rivet or bolt, whichever is the closest to the outside of the fire-protective construction, except that—

if the thickness of the fire protection is 40 mm or more, rivet heads may be disregarded; and

if the thickness of the fire protection is 50 mm or more—

any part of a bolt (other than a high-tensile bolt) may be disregarded; and

a column splice plate within 900 mm of the floor may encroach upon the fire protection by up to a ¼ of the thickness of the fire protection; and

the flange of a column or beam may encroach by up to 12 mm upon the thickness of the fire protection at right angles to the web if—

the column or beam is intended to have an FRL of 240/240/240 or 240/–/–; and

the flange projects 65 mm or more from the web; and

the thickness of the edge of the flange (inclusive of any splice plate) is not more than 40 mm.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One S2C27.