Specification clause · NCC 2022 Volume One
S2C7 Plaster reinforcement
Specification 2 Descriptions of elements referred to in Specification 1 · NCC 2019: Sch. 5 (Annex): 1.6
If plaster used as fire protection on walls is more than 19 mm thick—
it must be reinforced with expanded metal lath that—
has a mass per unit area of not less than 1.84 kg/m2; and
has not fewer than 98 meshes per metre; and
is protected against corrosion by galvanising or other suitable method; or
it must be reinforced with 13 mm x 13 mm x 0.7 mm galvanised steel wire mesh securely fixed at a distance from the face of the wall of not less than ⅓ of the total thickness of the plaster.
Same wording in NCC 2025 Volume One. See NCC 2025 Volume One S2C7.