Specification clause · NCC 2022 Volume One
S3C6 Smaller specimen permitted
Specification 3 Fire hazard properties · NCC 2019: Sch. 6: 2.5
A testing laboratory may carry out the test specified in S3C3(b) at pilot scale if a specimen (which must be not less than 900 mm x 900 mm) will adequately represent the proposed construction in the building, but the results of that test do not apply to construction larger than limits defined by the laboratory conducting the pilot examination.
Same wording in NCC 2025 Volume One. See NCC 2025 Volume One S3C6.