Specification clause · NCC 2022 Volume One

S40C2 Lighting timers

Specification 40 Lighting and power control devices · NCC 2019: Spec J6: 2

Open S40C2 on NCC Online ↗

A lighting timer must—

be located within 2 m of every entry door to the space; and

have an indicator light that is illuminated when the artificial lighting is off; and

not control more than—

an area of 100 m2 with a single push button timer; and

95% of the lights in spaces of area more than 25 m2; and

be capable of maintaining the artificial lighting—

for not less than 5 minutes; and

for not more than 12 hours if the timer is reset.

Changed in NCC 2025. See NCC 2025 Volume One S40C2, or show what changed.

A An artificial lighting timer manual switch must — be located within 2 m of every entry door to in a visible and easily accessed position — in the space; and have room or space being switched; or in an indicator light that is illuminated when the artificial lighting is off; and not control more than — an area of 100 m2 with a single push button timer; and 95% adjacent room or space from where at least 90% of the lights in spaces of area more than 25 m2; and be capable of maintaining the artificial lighting — for not less than 5 minutes; and for not more than 12 hours if the timer being controlled is reset. visible.

Removed words are struck through; added words are highlighted. Comparison of the text only.