S40C2 Lighting timers
Specification 40 Lighting and power control devices · NCC 2019: Spec J6: 2
A lighting timer must—
be located within 2 m of every entry door to the space; and
have an indicator light that is illuminated when the artificial lighting is off; and
not control more than—
an area of 100 m2 with a single push button timer; and
95% of the lights in spaces of area more than 25 m2; and
be capable of maintaining the artificial lighting—
for not less than 5 minutes; and
for not more than 12 hours if the timer is reset.
Changed in NCC 2025. See NCC 2025 Volume One S40C2, or show what changed.
A An artificial lighting timer manual switch must — be located within 2 m of every entry door to in a visible and easily accessed position — in the space; and have room or space being switched; or in an indicator light that is illuminated when the artificial lighting is off; and not control more than — an area of 100 m2 with a single push button timer; and 95% adjacent room or space from where at least 90% of the lights in spaces of area more than 25 m2; and be capable of maintaining the artificial lighting — for not less than 5 minutes; and for not more than 12 hours if the timer being controlled is reset. visible.