S40C4 Motion detectors
Specification 40 Lighting and power control devices · NCC 2019: Spec J6: 4
(1) In a Class 2, 3 or 9c residential care building other than within a sole-occupancy unit, a motion detector must—
be capable of sensing movement such as by infra-red, ultrasonic or microwave detection or by a combination of these means; and
be capable of detecting a person before they are 1 m into the space; and
other than within a sole-occupancy unit of a Class 3 building, not control more than—
an area of 100 m2; and
95% of the lights in spaces of area more than 25 m2; and
be configured so that the lights are turned off when the space is unoccupied for more than 15 minutes; and
be capable of being overridden by a manual switch only enabling the lights to be turned off.
(2) In a Class 5, 6, 7, 8, 9a or 9b building, a motion detector must—
be capable of sensing movement such as by infra-red, ultrasonic or microwave detection or by a combination of these means; and
be capable of detecting—
a person before they have entered 1 m into the space; and
movement of 500 mm within the useable part of the space; and
not control more than—
in other than a carpark, an area of 500 m2 with a single sensor or group of parallel sensors; and
75% of the lights in spaces using high intensity discharge; and
be configured so that the lights are turned off when the space is unoccupied for more than 15 minutes; and
be capable of being overridden by a manual switch that only enables the lights to be turned off.
(3) When outside a building, a motion detector must—
be capable of sensing movement such as by pressure, infra-red, ultrasonic or microwave detection or by a combination of these means; and
be capable of detecting a person within a distance from the light equal to—
twice the mounting height; or
80% of the ground area covered by the light’s beam; and
not control more than five lights; and
be operated in series with a photoelectric cell or astronomical time switch so that the light will not operate in daylight hours; and
be configured so that the lights are turned off when the area is unoccupied for more than 15 minutes; and
have a manual override switch which is reset after a maximum period of 4 hours.
(4) When in a fire-isolated stairway, fire-isolated passageway or fire-isolated ramp, a motion detector must—
be capable of sensing movement such as by infra-red, ultrasonic or microwave detection or by a combination of these means; and
be capable of detecting—
movement of 500 mm within the useable part of the space; and
a person before they have entered 1 m into the space; and
be configured so that the lights dim to a 30% peak power or less when the space is unoccupied for more than 15 minutes.
Changed in NCC 2025. See NCC 2025 Volume One S40C4, or show what changed.
(1) In a Class 2, 3 or 9c residential care building other than within a sole-occupancy unit, a motion detector A demand-operated control must — be capable activate artificial lighting upon detecting the presence or movement of sensing movement such as by infra-red, ultrasonic an occupant; and deactivate artificial lighting immediately or microwave detection or by after a combination of these means; and be capable of detecting a person before they are 1 m into the space; and other than within a sole-occupancy unit of a Class 3 building, run-on period not control more than — an area of 100 m2; and 95% of the lights in spaces of area more than 25 m2; and be configured so that the lights are turned off when 15 minutes after the space is unoccupied for more than 15 minutes; and be capable of being overridden by a manual switch only enabling the lights to be turned off. vacated. (2) In a Class 5, 6, 7, 8, 9a or 9b building, a motion detector must — be capable of sensing movement such as by infra-red, ultrasonic or microwave detection or by a combination of these means; and be capable of detecting — a person before they have entered 1 m into the space; and movement of 500 mm within the useable part of the space; and not A demand-operated control more than — in other than a carpark, an area of 500 m2 with a single sensor or group of parallel sensors; and 75% of the lights in spaces using high intensity discharge; and be configured so that the lights are turned off when the space is unoccupied for more than 15 minutes; and be capable of being overridden by a manual switch that only enables the lights to be turned off. (3) When outside a building, a motion detector must — be capable of sensing movement such as by pressure, infra-red, ultrasonic or microwave detection or by a combination of these means; and be capable of detecting a person within a distance from the light equal to — twice the mounting height; or 80% of the ground area covered by the light’s beam; and not control more than five lights; and be operated in series with a photoelectric cell or astronomical time switch so that the light will not operate in daylight hours; and be configured so that the lights are turned off when the area is unoccupied for more than 15 minutes; and have a manual override switch which is reset after a maximum period of 4 hours. (4) When in a fire-isolated stairway, fire-isolated passageway or fire-isolated ramp, a motion detector ramp must — be capable of sensing movement such as by infra-red, ultrasonic or microwave detection or by a combination of these means; and be capable of detecting — movement of 500 mm within the useable part of the space; and a person before they have entered 1 m into the space; and be configured so that a minimum of 30% of the lights dim to full design illumination is provided when deactivation required by (1)(b) has occurred. Notes For the purposes of S40C4, demand-operated controls may detect the presence or movement of an occupant via a 30% peak power motion detector, key card, security system or less when the space is unoccupied for more than 15 minutes. like.