Specification clause · NCC 2022 Volume One
S43C4 Separation from allotment boundaries and carparking areas
Specification 43 Bushfire protection for certain Class 9 buildings
(1) The building must be located not less than 10 m from any allotment boundary or open carparking area/spots.
(2) The separation distance required by (1) need not be complied with if the building is constructed—
with external walls that have an FRL of not less than 60/60/60 when tested from the outside, including any openings protected in accordance with AS 3959 for BAL—19 or greater; or
for external walls and roof, using a material or system that satisfies the test criteria of AS 1530.8.1 for a radiant heat flux of 10 kW/m² or greater.
Same wording in NCC 2025 Volume One. See NCC 2025 Volume One S43C4.