Specification clause · NCC 2022 Volume One

S43C6 Non-combustible path around building

Specification 43 Bushfire protection for certain Class 9 buildings

Open S43C6 on NCC Online ↗

A non-combustible pathway directly adjacent to the building and not less than 1.5 m wide must be provided around the perimeter of the building.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One S43C6.