Specification clause · NCC 2022 Volume One

S43C9 Internal tenability

Specification 43 Bushfire protection for certain Class 9 buildings

Open S43C9 on NCC Online ↗

To maintain internal tenability throughout the duration of occupancy during a bushfire event, the building must comply with the following:

An air handling system must be provided that is capable of—

being adjusted for full recycling of internal air for a period of not less than 4 hours to avoid the introduction of smoke into the building; and

maintaining an internal air temperature of not more than 25°C.

The building envelope must be designed such that if an air handling system required by (a) fails, then—

internal air temperatures can be maintained below 39°C; and

internal surface temperatures can be maintained below 60°C.

If the building is divided into separate compartments then, for the purposes of (a), each compartment must have a separate air handling system.

Each air handling system required by (a) must be designed to account for the activation of smoke detectors from low concentrations of smoke from external sources, so as to ensure that air-conditioning and other essential systems remain operational.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One S43C9.

Defined terms used