Specification clause · NCC 2022 Volume One
S44C2 Heating load limit
Specification 44 Calculation of heating load limit, cooling load limit and thermal energy load limit
The heating load limit of a space, measured in MJ/m2.annum, is equal to the greater of—
4; and
[formula] , where—
[formula] = the total annual heating degree hours of the building location; and
[formula] = the area adjustment factor for the heating load limit, determined in accordance with Table S44C2.
Table S44C2 Area adjustment factors for the heating load limit
Total area of habitable rooms (AH)
Area adjustment factor (FH)
≤ 50 m2
1.37
> 50 m2 to ≤ 350 m2
[formula] | > 350 m2
0.84
Tables
Same wording in NCC 2025 Volume One. See NCC 2025 Volume One S44C2.