Specification clause · NCC 2022 Volume One

S5C2 Exposure to fire-source features

Specification 5 Fire-resisting construction · NCC 2019: Spec C1.1: 2.1

Open S5C2 on NCC Online ↗

(1) A part of a building element is exposed to a fire-source feature if any of the horizontal straight lines between that part and the fire-source feature, or vertical projection of the feature, is not obstructed by another part of the building that—

has an FRL of not less than 30/–/–; and

is neither transparent nor translucent.

(2) A part of a building element is not exposed to a fire-source feature if the fire-source feature is—

an external wall of another building that stands on the allotment and the part concerned is more than 15 m above the highest part of that external wall; or

a side or rear boundary of the allotment and the part concerned is below the level of the finished ground at every relevant part of the boundary concerned.

(3) If various distances apply for different parts of a building element—

the entire element must have the FRL applicable to that part having the least distance between itself and the relevant fire-source feature; or

each part of the element must have the FRL applicable according to its individual distance from the relevant fire-source feature.

(4) The requirements of (3) do not override or permit any exemption from S5C3.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One S5C2.