S8C3 General requirements for external wall panels
Specification 8 Performance of external walls in fire · NCC 2019: Spec C1.11: 3
(1) Cast-in inserts and fixings must be anchored into the panel with welded bars or be fixed to the panel reinforcement.
(2) Cast-in inserts for top connections and fixings acting together must be able to resist an ultimate load of two times the larger of the forces required to develop—
the ultimate bending moment capacity of the panel at its base; or
the overturning moment at the base of the panel arising from an outwards lateral displacement at the top of the panel equal to one tenth of the panel height.
(3) Top connections of the panel exposed to fire, such as clips and drilled-in inserts, acting together must be able to resist an ultimate load of six times the larger of the forces required to develop the moment specified in (2)(a) or (b).
(4) Lateral supporting members and their connections must be designed to resist the connection forces specified in (2) and (3) and in the case of an eaves tie member the force in the member must be determined assuming that it deforms in a manner compatible with the lateral displacement of the wall panels, and that it acts in tension only.
(5) External wall panels that span vertically must have at least two upper connections per panel to the supporting member, except that where a number of panels are designed to act as one unit, (e.g. tongue and groove hollow-core panels), only two upper connections are required for each unit.
(6) External wall panels that span horizontally between columns must have at least two connections at each column.
(7) Connections providing lateral support to a panel must be designed to remain engaged to the supported panel both before and during a fire.
Notes
The increased forces specified by the multiplier of two or six in (2) and (3) above are to take account of the lower strength of the connections and members at the higher than ambient temperatures expected in a fire.