Table S36C2m Typical R-Values for non-ventilated roof spaces with a reflective surface: Pitched roof with cathedral ceiling, roof space not more than 300 mm thick

Specification 36 Material properties

Open Table S36C2m on NCC Online ↗
Emittance of airspace bounding surfacesThickness of roof spaceDirection of heat flowR-Value of reflective airspace
15° to not more than 25° pitchmore than 25° to not more than 35° pitchmore than 35° to not more than 45° pitch
Surface 1 emittance 0.9, Surface 2 emittance 0.05≤ 300 mmUp0.430.430.43
Surface 1 emittance 0.9, Surface 2 emittance 0.0520 mmDown0.590.590.59
Surface 1 emittance 0.9, Surface 2 emittance 0.0560 mmDown0.910.820.75
Surface 1 emittance 0.9, Surface 2 emittance 0.05100 mm to ≤ 300 mmDown0.960.850.76

Table Notes

A non-ventilated airspace in a roof is one with continuous cover, such as metal or sarked tiles, and no specific provision for ventilation.

Linear interpolation may be used to calculate the R-Value of the airspace in a roof with an intermediate pitch.

R-Values are calculated using AS/NZS 4859.2 based on the following:

summer temperatures of 24°C internally and 36°C externally for heat transfer down; and

winter temperatures of 18°C internally and 12°C externally for heat transfer up; and

emittances are normal emittances of bounding surfaces in accordance with AS 4200.1.

Table for S36C2 Construction Deemed-to-Satisfy