Table · NCC 2022 Volume One

Table S9C2 Cavity barrier requirements

Specification 9 Cavity barriers for fire-protected timber

Open Table S9C2 on NCC Online ↗
System required FRL–/60/60 or –/90/90–/120/120, –/180/180 or –/240/240
Cavity barrier required FRL–/45/45–/60/60
Timber, required minimum thickness45 mm60 mm
Mineral wool, required minimum thickness45 mm60 mm

Table Notes

Minimum thicknesses are to be measured in the direction of heat flow.

Table for S9C2 Requirements

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One Table S9C2.