B2P6 Legionella control
Part B2 Heated water services · NCC 2019: BP2.5
Heated water must be stored and delivered under conditions which avoid the likelihood of the growth of a Legionella bacteria count greater than or equal to 10 Legionella colony forming units (cfu) per millilitre.
Changed in NCC 2025. See NCC 2025 Volume Three B2P6, or show what changed.
Heated Containers used for producing and/or storing heated water must be stored are to relieve excessive pressure and delivered under conditions which avoid flash steam production by — relieving pressure so that the likelihood maximum rated working pressure, or 1400 kPa, whichever is the lesser, is not exceeded; and limiting water temperatures to a maximum of 99°C; or other suitable means providing an equivalent level of safety to (a) and (b). Applications B2P6(a) has a tolerance of +5% or 14 kPa whichever is the growth of a Legionella bacteria count greater than or equal to 10 Legionella colony forming units (cfu) per millilitre. greater.