Performance Requirement · NCC 2022 Volume Three

B3P5 Pressure

Part B3 Non-drinking water services · NCC 2019: BP3.3

Open B3P5 on NCC Online ↗

The points of discharge for a non-drinking water service must—

have—

a working pressure of not less than 50 kPa; and

a static pressure within the building of not more than 500 kPa: or

have water pressures suitable for the correct functioning of the fixture or appliance where water pressures outside of (a)(i) and (a)(ii) are required.

Changed in NCC 2025. See NCC 2025 Volume Three B3P5, or show what changed.

The points Means of discharge for isolation must be provided to a non-drinking water service must — have — a working pressure of not less than 50 kPa; and a static pressure within the building of not more than 500 kPa: or have water pressures suitable for the correct functioning of the fixture or appliance where water pressures outside of (a)(i) components that require testing, maintenance and (a)(ii) are required. replacement including mechanical devices, appliances and controls.

Removed words are struck through; added words are highlighted. Comparison of the text only.