Performance Requirement · NCC 2022 Volume Three

B4P2 Access and isolation

Part B4 Fire-fighting water services · NCC 2019: BP4.1

Open B4P2 on NCC Online ↗
Varied in VIC. Check the variation for your state.

(1) A fire-fighting water service must ensure access for maintenance of mechanical components and operational controls.

(2) A fire-fighting water service must ensure the system can be isolated for testing and maintenance.

Changed in NCC 2025. See NCC 2025 Volume Three B4P2, or show what changed.

(1) A Access must be provided to components of a fire-fighting water service must ensure access for that require testing, maintenance of or replacement, including mechanical components devices and operational controls. (2) A fire-fighting water service must ensure the system can be isolated for testing and maintenance.

Removed words are struck through; added words are highlighted. Comparison of the text only.