Deemed-to-Satisfy Provision · NCC 2022 Volume Three

D1D3 Sound insulation

Part D1 Excessive noise · NCC 2019: D1.3

Open D1D3 on NCC Online ↗
Varied in NT. Check the variation for your state.

(1) If a plumbing or drainage system serves or passes through more than one sole-occupancy unit in a Class 2, Class 3 or Class 9c building, it must be separated from the rooms of any other sole-occupancy unit by construction with an Rw + Ctr (airborne) not less than—

40 if the adjacent room is a habitable room (other than a kitchen); or

25 if the adjacent room is a kitchen or a non-habitable room.

(2) In Class 2, Class 3 or Class 9c buildings, a flexible coupling must be used to connect a pump to a plumbing or drainage system.

(3) If a plumbing or drainage system is located in (or passes through) a separating wall in a Class 1 building, it must—

only be installed in discontinuous construction; and

not be fixed to the wall of a dwelling that it does not serve; and

have a gap not less than 10 mm between the pipe and a wall of a dwelling that it does not serve; and

not be chased in if the separating wall is made of concrete or masonry.

Same wording in NCC 2025 Volume Three. See NCC 2025 Volume Three D1D3.
Can't meet D1D3? A Performance Solution must meet the Performance Requirements it satisfies: D1P1. Start a Performance Solution →

State and territory variations all clauses side by side →