D1D3 Sound insulation
Part D1 Excessive noise · NCC 2019: D1.3
(1) If a plumbing or drainage system serves or passes through more than one sole-occupancy unit in a Class 2, Class 3 or Class 9c building, it must be separated from the rooms of any other sole-occupancy unit by construction with an Rw + Ctr (airborne) not less than—
40 if the adjacent room is a habitable room (other than a kitchen); or
25 if the adjacent room is a kitchen or a non-habitable room.
(2) In Class 2, Class 3 or Class 9c buildings, a flexible coupling must be used to connect a pump to a plumbing or drainage system.
(3) If a plumbing or drainage system is located in (or passes through) a separating wall in a Class 1 building, it must—
only be installed in discontinuous construction; and
not be fixed to the wall of a dwelling that it does not serve; and
have a gap not less than 10 mm between the pipe and a wall of a dwelling that it does not serve; and
not be chased in if the separating wall is made of concrete or masonry.