S2C26 Reinforcing for column and beam protection — gypsum-perlite or gypsum-vermiculite plaster sprayed to contour
Specification 2 Descriptions of elements referred to in Specification 1 · NCC 2019: Sch. 5 (Annex): 11.4
(1) If a steel column or steel beam is protected with either gypsum-perlite or gypsum-vermiculite plaster sprayed to contour and the construction falls within the limits of Table S2C26a or S2C26b, the plaster must be reinforced with—
expanded metal lath complying with S2C7; or
galvanised steel wire mesh complying with S2C7.
(2) The reinforcement must be placed at a distance from the face of the plaster of at least 1/3 of the thickness of the plaster and must be securely fixed to the column or beam at intervals of not more than the relevant listing in Tables S2C26a and S2C26b.
(3) For the purposes of Tables S2C26a and S2C26b—
“vertical” includes a surface at not more than 10º to the vertical; and
“horizontal” includes a surface at not more than 10º to the horizontal; and
“underside” means the underside of any horizontal or non-vertical surface.
Table S2C26a Reinforcement of gypsum-perlite or gypsum-vermiculite plaster sprayed to contour — vertical members with H or I cross-section
Surface to be protected
Reinforcement required if smaller dimension of surface exceeds (mm)
Max spacing of fixings of the mesh to surface (mm)
Vertical
450
450
Non-vertical
300
300
Underside
300
300
Upper side of a horizontal surface
Not required
N/A
Table S2C26b Reinforcement of gypsum-perlite or gypsum-vermiculite plaster sprayed to contour — vertical members with other shapes
Surface to be protected
Reinforcement required if smaller dimensions of surface exceeds (mm)
Max spacing of fixings of the mesh to surface (mm)
Vertical
Any size
450
Non-vertical
Any size
300
Undersize
Any size
300
Upper side of a horizontal surface
Not required
N/A
Tables
- Table S2C26a Reinforcement of gypsum-perlite or gypsum-vermiculite plaster sprayed to contour — vertical members with H or I cross-section
- Table S2C26b Reinforcement of gypsum-perlite or gypsum-vermiculite plaster sprayed to contour — vertical members with other shapes