S41C7 Fire-fighting water services

Specification 41 Cross-connection hazards · NCC 2019: BS5.1.7

Open S41C7 on NCC Online ↗

(1) The following fire-fighting water services are Low Hazard:

A fire-fighting water service which has—

a direct connection to a Network Utility Operator's water supply; and

does not contain a tank, reservoir, connection to another water supply, antifreeze or other additives, or fire brigade booster connection from an auxiliary water supply,

Domestic fire sprinkler systems installed in Class 1 buildings.

FPAA101D fire sprinkler systems.

Fire-fighting water storage tanks.

(2) Any fire-fighting water services not referred to in (1) are Medium Hazard.

Notes

Fire hose reels located within an area where a cross-connection hazard exists have a Hazard Rating the same as the areas within reach of the hose.

Not in NCC 2025. No S41C7 in NCC 2025 Volume Three.