NCC 2022 Volume Two
Specification 44 Calculation of heating load limit, cooling load limit and thermal energy load limit
6 clauses · Open on NCC Online ↗
- S44C1 ScopeThis Specification contains the method of calculating the heating load limit, cooling load limit and thermal energy load limit for compliance with…
- Table S44C2 Area adjustment factors for the heating load limitTotal area of habitable rooms (AH) | Area adjustment factor (FH) ≤ 50 m2 | 1.37 > 50 m2 to ≤ 350 m2 | > 350 m2 | 0.84
- S44C2 Heating load limitThe heating load limit of a space, measured in MJ/m2.annum, is equal to the greater of— 4; and [formula] , where— [formula] = the total annual…
- Table S44C3 Area adjustment factors for the cooling load limitTotal area of the habitable rooms (AH) | Area adjustment factor (FC) ≤ 50 m2 | 1.34 > 50 m2 and ≤ 200 m2 | > 200 m2 and ≤ 1000 m2 | > 1000 m2 | 0.71
- S44C3 Cooling load limitThe cooling load limit of a space, measured in MJ/m2.annum, is calculated in accordance with the following formula: [formula] (2) In the formula at…
- S44C4 Thermal energy load limitThe thermal energy load limit of a space, measured in MJ/m2.annum, is calculated in accordance with the following formula: [formula] (2) In the…