Housing Provisions clause · ABCB Housing Provisions 2025

10.2.5 Other areas

Part 10.2 Wet area waterproofing · NCC 2019: Table 3.8.1.1

Open 10.2.5 on NCC Online ↗

(1) For walls adjoining other types of vessels (e.g. sink, basin or laundry tub), the following applies:

Walls must be water resistant to a height of not less than 150 mm above the vessel, for the extent of the vessel, where the vessel is within 75 mm of a wall (see Figure 10.2.5).

Waterproof wall junctions where a vessel is fixed to a wall.

Waterproof tap and spout penetrations where they occur in surfaces required to be waterproof or water resistant.

(2) For laundries and WCs, the following applies:

The floor of the room must be water resistant.

Wall/floor junctions must be water resistant, and where a flashing is used, the horizontal leg must not be less than 40 mm.

(3) For WCs with handheld bidet spray installations, the following applies:

The floor of the room must be waterproof.

Walls must be—

waterproof in WC area within a 900 mm radius from the wall connection of the handheld bidet spray device to a height of not less than 150 mm above the floor substrate; and

water resistant in WC area within a 900 mm radius from the wall connection of the handheld bidet device to not less than 1200 mm above the finished floor level of the WC.

Wall junctions within the WC area within 900 mm radius from the wall connection of the handheld bidet spray device must be waterproof.

Wall/floor junctions within the WC area within 1000 mm radius from the wall connection of the handheld bidet spray device must be waterproof.

Penetrations in the WC area must be waterproof.

Figure 10.2.5 Bath and vessel abutting wall — areas to be protected

Same wording in ABCB Housing Provisions 2022. See ABCB Housing Provisions 2022 10.2.5.

Defined terms used