Housing Provisions clause · ABCB Housing Provisions 2025

10.6.3 Location of sanitary compartments

Part 10.6 Ventilation · NCC 2019: 3.8.5.3

Open 10.6.3 on NCC Online ↗

A sanitary compartment must not open directly into a kitchen or pantry unless—

access is by an airlock, hallway or other room, (see Figure 10.6.3); or

the sanitary compartment is provided with an exhaust fan or other means of mechanical exhaust ventilation.

Figure 10.6.3 Acceptable location of non mechanically ventilated sanitary compartment

Same wording in ABCB Housing Provisions 2022. See ABCB Housing Provisions 2022 10.6.3.

Defined terms used