12.4.2 Open fireplace construction

Part 12.4 Heating appliances, fireplaces, chimneys and flues · NCC 2019: 3.10.7.2

Open 12.4.2 on NCC Online ↗

An open fireplace, or solid-fuel burning appliance in which the fuel-burning compartment is not enclosed must have—

all masonry constructed in accordance with H1D5; and

a hearth constructed of stone, concrete, masonry or similar non-combustible material so that—

it extends not less than 300 mm beyond the front of the fireplace opening and not less than 150 mm beyond each side of that opening; and

its upper surface does not slope away from the back hearth (see Figure 12.4.2); and

combustible material, such as flooring or framing members below or around the external edge of the hearth, is situated not less than 150 mm from the upper surface of the hearth (see Figure 12.4.2); and

walls forming the sides and back of the fireplace up to a height of 300 mm above the underside of the arch or lintel which—

are constructed in 2 separate leaves of solid masonry with a total combined thickness not less than 180 mm, excluding any cavity; and

do not consist of concrete block masonry in the construction of the inner leaf; and

are constructed of masonry units with a net volume, excluding cored and similar holes, not less than 75% of their gross volume, measured on the overall rectangular shape of the units, and with an actual thickness of not less than 100 mm; and

the fireplace must be constructed on footings complying with 4.2.18.

Figure 12.4.2 Fireplace clearance from combustible materials

Same wording in ABCB Housing Provisions 2022. See ABCB Housing Provisions 2022 12.4.2.