Housing Provisions clause · ABCB Housing Provisions 2025

13.7.6 Artificial lighting

Part 13.7 Services · NCC 2019: 3.12.5.5

Open 13.7.6 on NCC Online ↗

(1) The lamp power density or illumination power density of artificial lighting, excluding heaters that emit light, must not exceed the allowance of—

5 W/m2 in a Class 1 building; and

4 W/m2 on a verandah, balcony or the like attached to a Class 1 building; and

3 W/m2 in a Class 10a building associated with a Class 1 building.

(2) The illumination power density allowance in (1) may be increased by dividing it by the relevant illumination power density adjustment factor for a control device in (6) as applicable.

(3) When designing the lamp power density or illumination power density, the power of the proposed installation must be used rather than nominal allowances for exposed batten holders or luminaires.

(4) If halogen lamps are installed, they must be separately switched from fluorescent lamps.

(5) Artificial lighting around the perimeter of a building must—

be controlled by a daylight sensor; or

have an average light source efficacy of not less than 40 Lumens/W.

(6) The following illumination power density adjustment factors apply to control devices for artificial lighting:

Lighting timer for corridor lighting: 0.7.

Motion detector —

0.9, where —

at least 75% of the area of a space is controlled by one or more motion detectors; or

an area of less than 200 m2 is switched as a block by one or more motion detectors; and

0.7, where up to 6 lights are switched as a block by one or more detectors; and

0.55, where up to 2 lights are switched as a block by one or more detectors.

Manual dimming system where not less than 75% of the area of a space is controlled by manually operated dimmers: 0.85.

Programmable dimming system where not less than 75% of the area of a space is controlled by programmable dimmers: 0.85.

Dynamic dimming system, with automatic compensation for lumen depreciation, the design lumen depreciation factor is not less than —

0.9 for fluorescent lights; or

0.8 for high pressure discharge lights.

Fixed dimming where at least 75% of the area is controlled by fixed dimmers that reduce the overall lighting level and the power consumption of the lighting — equal to the % of full power to which the dimmer is set divided by 0.95.

Daylight sensor and dynamic lighting control device, with dimmed or stepped switching of lights adjacent to windows:

Lights within the space adjacent to windows other than roof lights for a distance from the window equal to the depth of the floor at window head height: 0.5.

Lights within the space adjacent to roof lights: 0.6.

(7) For the purposes of (6)(c), manual dimming is where lights are controlled by a knob, slider or other mechanism or where there are pre-selected scenes that are manually selected.

(8) For the purposes of (6)(d), programmed dimming is where pre-selected scenes or levels are automatically selected by the time of day, photoelectric cell or occupancy sensor.

(9) For the purposes of (6)(e), dynamic dimming is where the lighting level is varied automatically by a photoelectric cell to either proportionately compensate for the availability of daylight or the lumen depreciation of the lamps.

(10) For the purposes of (6)(f), fixed dimming is where lights are controlled to a level and that level cannot be adjusted by the user.

(11) For the purposes of (6)(g)(i) and (ii), the illumination power density adjustment factor is only applied to lights controlled by that item — this adjustment factor does not apply to tungsten halogen or other incandescent sources.

Same wording in ABCB Housing Provisions 2022. See ABCB Housing Provisions 2022 13.7.6.

Defined terms used