9.3.1 Separating walls
Part 9.3 Fire protection of separating walls and floors · NCC 2019: 3.7.3.2
(1) A separating wall between Class 1 buildings, or a wall that separates a Class 1 building from a Class 10a building which is not associated with the Class 1 building must—
be constructed—
having an FRL of not less than 60/60/60; or
of masonry not less than 90 mm thick; and
commence at the footings or ground slab (see Figure 9.3.1a), except for horizontal projections to which 9.3.4 applies (see Figure 9.3.4); and
extend—
if the building has a non-combustible roof covering, to the underside of the roof covering (see Figure 9.3.1a and Figure 9.3.1b); or
if the building has a combustible roof covering, to not less than 450 mm above the roof covering (see Figure 9.3.1a); and
comply with (2) to (5) and 9.3.2 as applicable.
(2) A separating wall of lightweight construction must be tested in accordance with Specification 6.
(3) A separating wall complying with (1)(c)(i)—
must not be crossed by timber or other combustible building elements except for roof battens with dimensions of 75 x 50 mm or less, or roof sarking; and
must have any gap between the top of the wall and the underside of the roof covering packed with mineral fibre or other suitable fire-resisting material.
(4) Where a building has a masonry veneer external wall, any gap between the separating wall and the external masonry veneer must be—
not more than 50 mm; and
packed with a mineral fibre or other suitable fire-resisting material with the packing arranged to maintain any weatherproofing requirements of H2D4.
(5) Eaves, verandahs and similar spaces that are open to the roof space and are common to more than one Class 1 dwelling must be separated by a non-combustible vertical lining (see Figure 9.3.1c).
Figure 9.3.1a Separating wall construction
Figure 9.3.1b Separating wall construction — Underside of non-combustible roof cladding (diagram 1)
Figure 9.3.1c Separating wall construction — Underside of non-combustible roof cladding (diagram 2)
Figure Notes
Elements crossing the non-combustible vertical lining must comply with 9.3.1(3).