South Australia variation · ABCB Housing Provisions 2025

SA 10.2.33 Provision of floor wastes

SA Part 10.2 Wet area waterproofing

Open on NCC Online ↗

Insert SA clause 10.2.33 in clause 10.2.33 as follows:

(1) The floor of a wet area containing a vessel must be graded to a floor waste to permit drainage of water.

(2) A floor need not be graded to the floor waste as required by (1) if—

all vessels are provided with in-built overflow protection or have a permanent open trapped connection to the plumbing and drainage system (such as a WC pan); or

the floor waste is provided solely for the connection of plumbing fixtures and all vessels in the wet area are provided with in-built overflow protection or have permanent open trapped connection to the plumbing and drainage system (such as a WC pan); or

flexible hose assemblies used for the connection of fixtures contained in the wet area must be fitted with flood stop safety valves approved under WMTS-479.

(3) A floor of a wet area that is graded without ponding to a floor waste within the shower area will satisfy (1).

(4) The fall of the floor surface graded to the floor waste in accordance with (1) or (3) must be in accordance with 10.2.12.

Changed since NCC 2022. See ABCB Housing Provisions 2022 SA 10.2.33, or show what changed.

Insert SA clause 10.2.33 in clause 10.2.33 as follows: (1) … to the plumbing and drainage system (such as a WC pan). pan); or flexible hose assemblies used for the connection of fixtures contained in the wet area must be fitted with flood stop safety valves approved under WMTS-479. (3) A floor of a wet area that is graded … with (1) or (3) must be in accordance with 10.2.12.

Removed words are struck through; added words are highlighted. Comparison of the text only.